C27 (60 Hz)

C27 Generator Set

C27 (60 HZ) 680-800 kW Diesel Generator models meet unique power needs while certified as a low fuel consumption system & EPA Stationary Emergency (Tier 2).

C27 (60 Hz)

DESCRIPTION

The C27 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 635 to 800 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and to take on 100 % rated load in one step. The C27 is certified as a low fuel consumption system as well as having a certificate for EPA Stationary Emergency (Tier 2).The C27 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 680 to 800 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and to take on 100 % rated load in one step. The C27 is certified as a low fuel consumption system as well as having a certificate for EPA Stationary Emergency (Tier 2). Seismic certification is also available for selected models, ensuring your generator sets are equipped for that unexpected disturbance. The integrated control system, including ATS and switchgear, ensures a consistent power supply and connection to your fleet through on-site and remote monitoring options. Our EMCP 4 control panel features a user-friendly interface and puts your management and diagnostics tools in one location. The EMCP 4.4 controller provides multi generator set paralleling capability, allowing you to use multiple generator sets for increased power output and improved reliability. It's not just quality that matters but customization, choose from a broad range of accessories and bolt-on system expansion attachments. Discover our upgradeable packaging options to work with your spatial restrictions and environmental conditions. Our C27 generator sets are developed for such prerequisites, so that you can meet your specific power needs. Build in additional safety features with the UL 2200 and CSA certified package options.Electric Power

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • UL 2200
  • CSA
  • IBC seismic certification
  • OSHPD pre-approval

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

  • Standard Equipment
  • Optional Equipment
  • Specs
  • Docs

Standard Equipment

  • Air Inlet
    • Air cleaner; single element canister type with service indicator
  • Control Panel
    • EMCP 4.2B
    • Digital Indicators
    • Warning/shutdown Indicators
    • Programmable protective relaying functions
    • Communications
    • Features include:
  • Cooling System
    • Coolant level sensor
    • Coolant drain line with valve terminated on edge of base
    • ATAAC
    • Caterpillar extended life coolant
    • Radiator sized to 50 degrees C
    • Fan and belt guards drive
  • Exhaust System
    • 203 mm (8 in) ID round flanged outlet
    • Exhaust manifold - dry
  • Fuel System
    • Primary fuel filter with integral water separator
    • Electric fuel priming pump
    • Fuel cooler
    • Flexible fuel lines - installed
    • Secondary fuel filters
  • Generators and Attachments
    • Integrated voltage regulator (IVR) includes
    • For EPA Stationary Emergency (EPA Tier 2 Emissions) configurations:
    • Busbar connections:
    • SR5 Permanent magnet excitation (PMG) (PM)
    • For Low BSFC configurations:
  • Lube System
    • Standard volume oil pan - 68 Ltr
    • Lubricating oil
    • Oil drain lines and valve
    • Gear type lube oil pump
    • Oil filter, filler and dipstick
    • Fumes disposal - open crankcase ventilation routed to front of package
    • Integral lube Oil cooler
  • Mounting System
    • Rubber anti-vibration mounts - shipped loose
    • Rails - engine/generator/radiator mounting
  • Starting and Charging System
    • 24-Volt electric starting motor
    • Battery, rack and cables - shipped-loose
    • Battery disconnect switch
    • Charging alternator 45A
  • General
    • Paint - Caterpillar yellow with high gloss black rails & radiator
    • SAE standard rotation
    • Right hand servicing
    • Flywheel and flywheel housing-SAE No. 0 and SAE No. 18

Optional Equipment

  • Air Inlet System
    • Standard air cleaners
    • Heavy duty air cleaners
    • Dual element air cleaners
  • Starting / Charging System
    • 20 Amp enclosure Battery chargers
    • 10 Amp Battery chargers
    • 24 Volt battery set - Dry
    • Air starting motor with control and silencer
    • Space heater
    • 24 Volt electric start motors - Heavy duty
    • Jacket water heaters
  • Circuit breakers
    • 400, 800, 1200, 1600, 2000, 2500, 3000 Amp, 3 pole, UL-100% rated Circuit breakers
    • 2000 Amp, 3 pole, IEC rated Circuit breakers
    • 800 Amp, 4 pole, IEC rated Circuit breakers
  • Control Panels
    • Cable shroud - Bottom mounted
    • Cable shroud - Top mounted
    • EMCP 4.3, EMCP4.4
    • Side extension box
    • Remote annunciator module
    • Auxiliary box options
    • Remote mounted panel harness mounting kit
    • Remote mounted circuit breaker terminals
    • Modbus monitor local packages
    • Remote DIO module
    • Cat connect telematics
    • Load share module
    • Vandal proof panel cover
    • Installed DIO module
    • Remote mounting harness
    • Annunciator modules
  • Cooling System
    • Radiator duct flange
    • High ambient radiator
    • Extended life coolant
    • Certified radiator
    • Standard radiator
  • Enclosures
    • Enclosure louvers
    • Enclosure with lifting base or fuel tank
    • Panel bracket
    • AC distribution panel, lights and outlet
    • Enclosure lighting
    • Enclosure colors
    • Special Sound attenuated enclosure
    • Enclosure fuel tank options
    • Cold weather bundle
  • Exhaust System
    • Mufflers
    • Elbows
    • Flanges
    • Exhaust through the wall kit
    • Flexible fittings
    • Guard and shield system
  • Generator and Attachments
    • 60 Hz standard generators
    • 60 Hz premium generators
  • Lube System
    • Prelube pumps
    • Oil level regulator
  • Mounting System
    • Mounting base type
    • IBC vibration isolators
    • Puck style low efficiency isolators
    • Spring type vibration isolators
  • Power Connections
    • Center post busbars
    • Cable entry - right/left/rear
    • Neutral grounding connection
    • Power connections - Right / Left / Rear
  • Special Tests / Reports
    • Torsional vibration analysis report
    • Generator test report
    • IBC seismic Certifications
    • OSHPD seismic Certifications
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
    • Special CSA test Certification
    • Standard engine test
  • General
    • Miscellaneous inspection
    • US aid emblem
    • Special paint
    • SGS Inspection

Specs

Overview

Long Name:
C27 Generator Set
Name:
C27 (60 Hz)
Brand:
Cat
Status:
Current

Generator Set Specifications

Maximum Rating
800 ekW
Minimum Rating
635 ekW
Emissions/Fuel Strategy
Low Fuel, Tier 2 Nonroad Equivalent
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime

Engine Specifications

Engine Model
C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel
Bore
5.4 in / 137.2 mm
Stroke
6 in / 152.4 mm
Displacement
1649.47 in³ / 27.03 l
Compression Ratio
16.1:1
Aspiration
TA
Fuel System
MEUI
Governor Type
Adem™A4

Generator Set Dimensions

Length - Maximum
184 in / 4674 mm
Width - Maximum
67.8 in / 1723 mm
Height - Maximum
85.1 in / 2162 mm

SEE HOW C27 (60 Hz) COMPARES AGAINST FREQUENTLY COMPARED PRODUCTS.

Diesel Generator Sets
C27 (60 Hz)
C27 (60 Hz)
Brand
Cat
Status
Current
Emissions/Fuel Strategy
Low Fuel, Tier 2 Nonroad Equivalent
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime
Engine Model
C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel
Bore
5.4 in / 137.2 mm
Stroke
6 in / 152.4 mm
Compression Ratio
16.1:1
Aspiration
TA
Fuel System
MEUI
Governor Type
Adem™A4
Length - Maximum
184 in / 4674 mm
Width - Maximum
67.8 in / 1723 mm
Height - Maximum
85.1 in / 2162 mm
Diesel Generator Sets
C2.2 | D30
D30
Brand
Cat
Status
Current
Emissions/Fuel Strategy
US EPA TIER 4I (EPA 40 CFR Part 1039 Interim Tier 4)
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Model
Cat® C2.2, In-line 4, 4-cycle diesel
Bore
3.3 in / 84 mm
Stroke
3.9 in / 100 mm
Compression Ratio
23.3:1
Aspiration
Turbocharged air to air charge cooling
Fuel System
Electronically actuated Mechanical Cassette type
Governor Type
Mechanical
Length - Maximum
88.6 in / 2250 mm
Width - Maximum
41.3 in / 1050 mm
Height - Maximum
57.9 in / 1470 mm
Diesel Generator Sets
C280-12
C280-12
Brand
Cat
Status
Current
Emissions/Fuel Strategy
EPA Tier 4 Final, IMO Tier 2
Frequency
50 / 60 Hz
Speed
900 / 1000 rpm
Duty Cycle
Prime, Continuous
Engine Model
C280-12, V-12,4-Stroke Water-Cooled Diesel
Bore
11 in / 280 mm
Stroke
11.8 in / 300 mm
Compression Ratio
13:01
Aspiration
TA
Fuel System
Direct unit injection
Governor Type
Generator Set Monitoring System (GMS)
Length - Maximum
404 in / 10261.7 mm
Width - Maximum
99.62 in / 2530.3 mm
Height - Maximum
156.6 in / 3977.7 mm