D100 GC

D100 GC Generator Set

D100 GC C4.4 (60 HZ) 100 kW Diesel Generator models represent a customizable and flexible solution for your standby applications.

D100 GC Open Set

DESCRIPTION

Producing reliable power of 100 ekW at 60 Hz, our D100 GC diesel generator sets designed to ISO 8528-5 transient response requirements. All D100 GC generator sets meet EPA Stationary Emergency (Tier 3) emissions standards.Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.Electric Power

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

M-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • UL 2200 Listed
  • ULC Certification Available

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

  • Standard Equipment
  • Optional Equipment
  • Specs
  • Docs

Standard Equipment

  • Air Inlet System
    • Air cleaner; light duty with disposable element
    • Air cleaner
  • Cooling System
    • Coolant drain line with valve
    • Radiator and cooling fan with guards
    • Caterpillar extended life coolant
    • Fan drive, battery charging alternator drive
  • Control Panel
    • GCCP 1.2 Control panel
  • Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
  • Fuel System
    • Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
  • Generator
    • Circuit breaker, IEC, 3 pole, mounted in tower panel
    • IP23 Protection
    • Tower panel, IP22, bottom cable entry
    • 12 Leads
    • Voltage regulator (single phase sensing)
    • Segregated low voltage (AC/DC) wiring panel
  • Governing System
    • Mechanical and electrical governing system - model dependent
  • Lube System
    • Lubricating oil
    • Oil drain line with valve
  • Mounting System
    • Termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
    • Includes lifting provision and drag points
  • Starting/Charging System
    • Batteries
    • 24V battery with rack and cables
  • General
    • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

  • Alternator System
    • Anti-condensation heater
    • 3 phase sensing
    • Permanent magnet excitation (PMG)
    • R Frame auxilliary winding
    • Quadrature droop kit
  • Circuit breakers
    • Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
  • Cooling System
    • Coolant heater
    • Low coolant temperature alarm
    • Low coolant level shutdown
  • Control Panel Options
    • Earth fault (2 wire only)
    • Control panel heater
    • GCCP 1.2 Control panel
    • Volt free contacts
    • Emergency stop with key
    • Voltage adjust potentiometer
    • Overload shutdown via breaker
    • Panel mounted audible alarm
    • Battery charger
    • Earth leakage (2 wire only)
    • Speed adjust potentiometer
  • Enclosures
    • Sound attenuated Level 2 enclosure
  • Fuel System
    • Low fuel level alarm
    • Bunded fuel tank
    • Low fuel level shutdown
    • High fuel level alarm
  • Mounting Options
    • Battery removal
    • Electronic governor
    • Industrial silencer
    • External single point lift - enclosure
    • Silencer installation kit
  • Special Packing/Inspectons for Shipment
    • PGS Test report @ 0.8 power factor
    • PGS Test report @ 1.0 power factor
  • General - Accessories / Miscellaneous
    • Packing case - canopied set
    • Packing case - compact set
    • Stone guards/rad trans flange

Specs

Overview

Long Name:
D100 GC Generator Set
Name:
D100 GC
Brand:
Cat
Status:
Current

Generator Set Specifications

Maximum Rating
100 ekW
Minimum Rating
100 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby

Engine Specifications

Engine Model
C4.4, In-line 4, 4-cycle diesel
Bore
4.1 in / 105 mm
Stroke
5 in / 127 mm
Displacement
269 in³ / 4.4 l
Compression Ratio
16.7:1
Aspiration
Turbocharged
Fuel System
Common Rail
Governor Type
Mechanical, ADEM™A4

Generator Set Dimensions

Length - Maximum
82.6 in / 2097 mm
Width - Maximum
43.3 in / 1100 mm
Height - Maximum
52.9 in / 1343 mm
Dry Weight - Genset (maximum)
2222 lb / 1008 kg

SEE HOW D100 GC COMPARES AGAINST FREQUENTLY COMPARED PRODUCTS.

Diesel Generator Sets
D100 GC
D100 GC Open Set
Brand
Cat
Status
Current
Maximum Rating
100 ekW
Minimum Rating
100 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Model
C4.4, In-line 4, 4-cycle diesel
Bore
4.1 in / 105 mm
Stroke
5 in / 127 mm
Displacement
269 in³ / 4.4 l
Compression Ratio
16.7:1
Aspiration
Turbocharged
Fuel System
Common Rail
Governor Type
Mechanical, ADEM™A4
Length - Maximum
82.6 in / 2097 mm
Width - Maximum
43.3 in / 1100 mm
Height - Maximum
52.9 in / 1343 mm
Diesel Generator Sets
C9 | DE330E0
C9 Open Generating Set Rear Right
Brand
Cat
Status
Current
Maximum Rating
330 kVA
Minimum Rating
330 kVA
Emissions/Fuel Strategy
Non-Certified
Voltage
200 to 400 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
Engine Model
C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
4.41 in / 112 mm
Stroke
5.87 in / 149 mm
Displacement
537.01 in³ / 8.8 l
Compression Ratio
16.1:1
Aspiration
Air to Air Aftercooled
Fuel System
Hydraulic electronic unit injection
Governor Type
Adem™A4
Length - Maximum
157 in / 3988 mm
Width - Maximum
47.5 in / 1207 mm
Height - Maximum
73.5 in / 1867 mm
Diesel Generator Sets
D1000 GC
DE1000 GC
Brand
Cat
Status
Current
Maximum Rating
1000 ekW
Minimum Rating
1000 ekW
Emissions/Fuel Strategy
U.S. EPA Tier 2
Voltage
380 - 480 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.71 in / 145 mm
Stroke
6.38 in / 162 mm
Displacement
1958.86 in³ / 32.1 l
Compression Ratio
15.0:1
Aspiration
TA
Fuel System
EUI
Governor Type
Adem™A4
Length - Maximum
164.3 in / 4175 mm
Width - Maximum
73.1 in / 1856 mm
Height - Maximum
87.3 in / 2217.5 mm