XQC1200
XQC1200
DESCRIPTION
This rental generator set extends the Caterpillar line of rental power options improving efficiency and reduced owning and operating costs. The XQC1200 is equipped with an enhanced control system, designed to reduce installation and startup time. It is configured to switch between 50 and 60Hz ratings at the press of a button. The control system features plant control programming and simulation, allowing complete system testing prior to generator set startup. Advanced product autonomy and monitoring capabilities reduce on-site manpower support requirements, minimize operator exposure to hazards, and permit site performance and maintenance data to be viewed, archived, and analyzed conveniently. Ideal in a stand-alone environment, combined with dozens of units in a power plant solution, or supporting utility systems worldwide.Rental Ready
Extensive range of rental ready features to meet job requirements and applications.
Fuel/Emissions Strategy
Low BSFC and Low Emissions* ratings, switchable via Cat Electronic Technician (ET) * Does not conform to EPA/EU emissions standards
Reliable, Fuel Efficient Cat Diesel Engine
The compact, four-cycle Cat 3512C turbocharged-aftercooled (SCAC) diesel engine provides proven durability and dependability Best-in-class fuel economy Fuel system operates on a variety of fuels 50/60 Hz switchable with neither software re-flashing, nor iron changes required Other engine features include: electric fuel priming, individual cylinder temperature monitoring, and extended filter change intervals
Cat EMCP Control Panel
EMCP 4.3 control panel offers engine and generator monitoring and protection On-Package Auto Paralleling Controls AGC-4 provides paralleling, load sharing, VFD control, and additional generator protection
Cat Generator
Cat SR500 generator designed to match the performance and output characteristics of the Cat Gas engine. Class H insulation operating at Class F temperature for extended life Coastal insulation protection and anti-condensation space heaters Integrated Voltage Regulator (IVR) for fast response in demanding applications
Cooling System
Provides 40°C (104F) ambient capability at 50 Hz, or 42°C (108F) capability at 60 Hz at the IPP Rating at 750m (2,460 ft) above sea level Variable frequency fan drive with smart fan control Energy efficient electric drive fans
Sound Attenuated Container
Meets 83 dB(A) (50 Hz) / 85 dBA (60 Hz) at 7m (23 ft) 20' ISO high cube container, 9-high stack CSC certified Service and Personnel doors Externally-accessible controls
Cat Connect
Remote monitoring for fleet management and asset tracking.
Reduced Environmental Impact
110% spill containment of onboard engine fluids Positive crankcase fumes ventilation
Single-Source Supplier
Generator set manufactured in ISO 9001:2000 compliant facility Package factory designed and production tested
Worldwide Product Support
Cat® dealers provide extensive post sale support including maintenance and repair agreements. Supported 100% by the Cat dealer with warranty on parts and labor. Extended Service Coverage (ESC) options available for coverage beyond the Standard Warranty period
- Standard Equipment
- Specs
- Docs
Standard Equipment
- Cat 3512C heavy duty diesel engine
- Heavy duty, dual element, PowerCore air cleaners with service indicators
- Secondary fuel filters
- Full flow oil filters with water-cooled oil cooler. Requires API CI-4 or higher lube oil
- Lubricating oil system includes make-up system (113-L tank), oil drain lines routed to the engine rail, and quick evacuation system for faster, cleaner oil changes
- Jacket water heater (9 kW, 3-phase 480VAC) with electric pump
- Fuel cooler and electric priming pump
- Electronic differential pressure monitoring of all filters
- Electronic ADEM™ A4 engine controls
- 24V electric starting motor
- SR5 Generator
- Double-bearing, SR-5 generator with anti-condensation space heaters (1.2 kW, 480VAC)
- Brushless, random-wound, permanent magnet excited, thouree-phase, 4-lead design
- Class H insulation operating at Class F temperature for extended life
- Cat Integrated Voltage Regulator (Cat IVR)
- Stator winding and bearing temperature sensors and RTD module
- Metallic mesh generator air inlet filters (washable) with differential pressure monitoring
- Coastal Insulation Protection
- 20' ISO high-cube container, 9-High stackable, CSC certified
- Hinged, radiator air intake louvers
- Sound-attenuated engine room air intake louvers with foldable awnings that double as shipping covers
- Two (2) lockable personnel doors with panic releases
- Interior walls and ceilings insulated with 50 mm of acoustic paneling
- Side bus bar access door with external access load cable connections
- Shore power via distribution block connections for jacket water heater, battery charger, and generator Anti-condensation Heaters
- Four (4) DC lights with 60-min timer
- Single-wall, 378-L (100gal) fuel tank; certified to BS799-5
- Solenoid fuel-fill control valve for automated tank filling
- Triple, primary fuel filters with integral water separators and service valves for on-the-fly changes
- Sound attenuated to 83 dBA (50 Hz) / 85 dBA (60 Hz) at 7m (23 ft)
- Two (2) 1400-CCA, Group 4D, maintenance-free batteries and 50-Amp battery charger
- Insulated exhaust silencer with 1.8m (6ft) stainless steel exhaust stack for increased site power density
- Engine vibration isolators
- Easy drain access to standard fluids
- Standard Cat decals and painted Cat Power Module White
- Cooling
- Cooling package provides 40°C (104F) ambient capability at 50 Hz, or 42°C (108F) capability at 60 Hz at the IPP Rating at 750m (2,460 ft) above sea level
- Vertical, non-stacked radiator cores with dimpled fins and vertical air discharge
- Variable frequency fan drive with smart fan control
- Cat Extended Life Coolant (ELC)
- Generator Controls and Protection
- EMCP 4.3 generator set mounted controller
- Automatic start/stop with cool down timer
- Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
- AGC-4 provides voltage and frequency adjust, base load / PF / load sharing / synchouronizer, auto start / stop control & generator CB control, SCADA Interface (Ethernet), fuel level Indications & alarms, and fuel tank fuel transfer control
- Reverse compatibility for interface to legacy power modules
- 100 kAIC, 4000A-Frame generator circuit breaker with LSIG trip unit
- Multi-mode operation: Island (kW/kVAR sharing), Base load power, Power management with multiple units
- Manual and automatic paralleling capability
- Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchouroscope
- Quality
- Factory testing of complete power module
- CE Certified, NEMA, ISO and IEEE standards
- O&M manuals
Specs
Overview
Generator Set
Engine
Dimensions
Generator Set
SEE HOW XQC1200 COMPARES AGAINST FREQUENTLY COMPARED PRODUCTS.
- Brand
- Caterpillar
- Status
- Current
- Frequency
- 50/60 Hz
- Voltage
- 230 - 480 V
- Engine
- Cat 3512C
- Fuel
- Diesel
- Brand
- Caterpillar
- Status
- Current
- Frequency
- 60 Hz
- Voltage
- 120 - 600 V
- Engine
- Cat C3.4
- Fuel
- Diesel
- Brand
- Caterpillar
- Status
- Current
- Frequency
- 50/60 Hz
- Voltage
- 230 - 480 V
- Engine
- Cat 3516C
- Fuel
- Diesel